Vulnerabilities · 2016 · Rockwellautomation
CVE-2016-9343
Rockwellautomation Softlogix 5800 Controller Firmware vulnerability
An issue was discovered in Rockwell Automation Logix5000 Programmable Automation Controller FRN 16.00 through 21.00 (excluding all firmware versions prior to FRN 16.00, which are not affected). By sending malformed common industrial protocol (CIP) packet, an attacker may be able to overflow a stack-based buffer and execute code on the controller or initiate a nonrecoverable fault resulting in a denial of service.
High priority: this vulnerability is rated critical and can be attacked over the network without a login.
Affected products
Softlogix 5800 Controller Firmware, Rslogix Emulate 5000 Firmware, Guardlogix 5570 Controller Firmware, Flexlogix L34 Controller Firmware, Controllogix L55 Controller Firmware, Controllogix 5570 Redundant Controller Firmware, Controllogix 5570 Controller Firmware, Controllogix 5560 Redundant Controller Firmware, Controllogix 5560 Controller Firmware, 1769 Compactlogix L3x Controller Firmware and more. The exact versions are in the references.
What to do now
- Check your exposureFind out whether Rockwellautomation Softlogix 5800 Controller Firmware runs anywhere in your environment, including systems of suppliers.
- UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
- Limit access until thenIf you cannot update at once, take the system off the internet or restrict who can reach it.
References
- www.securityfocus.com/bid/95304 · Third Party Advisory
- ics-cert.us-cert.gov/advisories/ICSA-16-343-05 · Third Party Advisory
- nvd.nist.gov/vuln/detail/CVE-2016-9343
- cve.org/CVERecord?id=CVE-2016-9343
More vulnerabilities in Rockwellautomation products
Data: CVE list and the NVD. This product uses data from the NVD API but is not endorsed or certified by the NVD.