CONTENTUM.COMA specialist. A plan. A result.

Vulnerabilities · 2017 · Schneider-electric

CVE-2017-7574
Schneider-electric Modicon Tm221ce16r Firmware vulnerability

Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product.

High priority: this vulnerability is rated critical and can be attacked over the network without a login.

Affected products

Modicon Tm221ce16r Firmware, Somachine. The exact versions are in the references.

What to do now

  • Check your exposureFind out whether Schneider-electric Modicon Tm221ce16r Firmware runs anywhere in your environment, including systems of suppliers.
  • UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
  • Limit access until thenIf you cannot update at once, take the system off the internet or restrict who can reach it.

References

More vulnerabilities in Schneider-electric products

Data: CVE list and the NVD. This product uses data from the NVD API but is not endorsed or certified by the NVD.