Vulnerabilities · 2018 · Siemens
CVE-2018-4858
Siemens Ec 61850 System Configurator Firmware vulnerability
A vulnerability has been identified in IEC 61850 system configurator (All versions < V5.80), DIGSI 5 (affected as IEC 61850 system configurator is incorporated) (All versions < V7.80), DIGSI 4 (All versions < V4.93), SICAM PAS/PQS (All versions < V8.11), SICAM PQ Analyzer (All versions < V3.11), SICAM SCC (All versions < V9.02 HF3). A service of the affected products listening on all of the host's network interfaces on either port 4884/TCP, 5885/TCP, or port 5886/TCP could allow an attacker to either exfiltrate limited data from the system or to execute code with Microsoft Windows user permissions. Successful exploitation requires an attacker to be able to send a specially crafted network request to the vulnerable service and a user interacting with the service's client application on the host. In order to execute arbitrary code with Microsoft Windows user permissions, an attacker must be able to plant the code in advance on the host by other means. The vulnerability has limited impact to confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.
Affected products
Ec 61850 System Configurator Firmware, Sicam Pq Analyzer Firmware, Sicam Scc Firmware, Digsi 4 Firmware, Digsi 5 Firmware, Sicam Pas\/pqs. The exact versions are in the references.
What to do now
- Check your exposureFind out whether Siemens Ec 61850 System Configurator Firmware runs anywhere in your environment, including systems of suppliers.
- UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
- Set the orderSystems that can be reached from the internet come first, then the rest.
References
- cert-portal.siemens.com/productcert/pdf/ssa-159860.pdf · Vendor Advisory
- www.securityfocus.com/bid/105933 · Third Party Advisory
- ics-cert.us-cert.gov/advisories/ICSA-18-317-01 · Third Party Advisory
- nvd.nist.gov/vuln/detail/CVE-2018-4858
- cve.org/CVERecord?id=CVE-2018-4858