Vulnerabilities · 2019 · Siemens
CVE-2019-13942
Siemens En100 Ethernet Module With Firmware Variant Dnp3 Tcp vulnerability
A vulnerability has been identified in EN100 Ethernet module DNP3 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.37), EN100 Ethernet module IEC104 variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). An unauthorized user could exploit a buffer overflow vulnerability in the webserver. Specially crafted packets sent could cause a Denial-of-Service condition and if certain conditions are met, the affected devices must be restarted manually to fully recover. At the time of advisory publication no public exploitation of this security vulnerability was known.
Affected products
En100 Ethernet Module With Firmware Variant Dnp3 Tcp, En100 Ethernet Module With Firmware Variant Iec 61850, En100 Ethernet Module With Firmware Variant Iec104, En100 Ethernet Module With Firmware Variant Modbus Tcp, En100 Ethernet Module With Firmware Variant Profinet Io. The exact versions are in the references.
What to do now
- Check your exposureFind out whether Siemens En100 Ethernet Module With Firmware Variant Dnp3 Tcp runs anywhere in your environment, including systems of suppliers.
- UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
- Limit access until thenIf you cannot update at once, take the system off the internet or restrict who can reach it.
References
More vulnerabilities in Siemens products
Data: CVE list and the NVD. This product uses data from the NVD API but is not endorsed or certified by the NVD.