Vulnerabilities · 2020 · Automationdirect
CVE-2020-10920
Automationdirect C-more Hmi Ea9 Firmware vulnerability
This vulnerability allows remote attackers to execute arbitrary code on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The specific flaw exists within the control service, which listens on TCP port 9999 by default. The issue results from the lack of authentication prior to allowing alterations to the system configuration. An attacker can leverage this vulnerability to execute code in the context of the device. Was ZDI-CAN-10493.
High priority: this vulnerability is rated critical and can be attacked over the network without a login.
Affected products
C-more Hmi Ea9 Firmware. The exact versions are in the references.
What to do now
- Check your exposureFind out whether Automationdirect C-more Hmi Ea9 Firmware runs anywhere in your environment, including systems of suppliers.
- UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
- Limit access until thenIf you cannot update at once, take the system off the internet or restrict who can reach it.
References
More vulnerabilities in Automationdirect products
Data: CVE list and the NVD. This product uses data from the NVD API but is not endorsed or certified by the NVD.