CONTENTUM.COMA specialist. A plan. A result.

Vulnerabilities · 2020 · Beckhoff

CVE-2020-12510
Beckhoff Twincat Extended Automation Runtime vulnerability

The default installation path of the TwinCAT XAR 3.1 software in all versions is underneath C:\TwinCAT. If the directory does not exist it and further subdirectories are created with permissions which allow every local user to modify the content. The default installation registers TcSysUI.exe for automatic execution upon log in of a user. If a less privileged user has a local account he or she can replace TcSysUI.exe. It will be executed automatically by another user during login. This is also true for users with administrative access. Consequently, a less privileged user can trick a higher privileged user into executing code he or she modified this way. By default Beckhoff’s IPCs are shipped with TwinCAT software installed this way and with just a single local user configured. Thus the vulnerability exists if further less privileged users have been added.

Affected products

Twincat Extended Automation Runtime. The exact versions are in the references.

What to do now

  • Check your exposureFind out whether Beckhoff Twincat Extended Automation Runtime runs anywhere in your environment, including systems of suppliers.
  • UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
  • Set the orderSystems that can be reached from the internet come first, then the rest.

References

More vulnerabilities in Beckhoff products