CONTENTUM.COMA specialist. A plan. A result.

Vulnerabilities · 2021 · Siemens

CVE-2021-41545
Siemens Desigo Dxr2 Firmware vulnerability

A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). When the controller receives a specific BACnet protocol packet, an exception causes the BACnet communication function to go into a “out of work” state and could result in the controller going into a “factory reset” state.

Affected products

Desigo Dxr2 Firmware, Desigo Pxc3 Firmware, Desigo Pxc4 Firmware, Desigo Pxc5 Firmware. The exact versions are in the references.

What to do now

  • Check your exposureFind out whether Siemens Desigo Dxr2 Firmware runs anywhere in your environment, including systems of suppliers.
  • UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
  • Limit access until thenIf you cannot update at once, take the system off the internet or restrict who can reach it.