CONTENTUM.COMA specialist. A plan. A result.

Vulnerabilities · 2022 · Honeywell

CVE-2022-30316
Honeywell Safety Manager Firmware vulnerability

Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthenticated firmware update issue. The affected components are characterized as: Firmware update functionality. The potential impact is: Firmware manipulation. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 communication FTA serial interface and Enea POLO bootloader for firmware management purposes. An engineering workstation running the Safety Builder software communicates via serial or serial-over-ethernet link with the DCOM-232/485 interface. Firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks. Firmware images are unsigned. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize hardcoded credentials (see FSCT-2022-0052) for the POLO bootloader to control the boot process and push malicious firmware images to the controller allowing for firmware manipulation, remote code execution and denial of service impacts. A mitigating factor is that in order for a firmware update to be initiated, the Safety Manager has to be rebooted which is typically done by means of physical controls on the Safety Manager itself. As such, an attacker would have to either lay dormant until a legitimate reboot occurs or possibly attempt to force a reboot through a secondary vulnerability.

Affected products

Safety Manager Firmware. The exact versions are in the references.

What to do now

  • Check your exposureFind out whether Honeywell Safety Manager Firmware runs anywhere in your environment, including systems of suppliers.
  • UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
  • Set the orderSystems that can be reached from the internet come first, then the rest.

References

More vulnerabilities in Honeywell products

Data: CVE list and the NVD. This product uses data from the NVD API but is not endorsed or certified by the NVD.