CVE-2022-33174
Powertekpdus Basic Pdu Firmware vulnerability
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
High priority: this vulnerability is rated critical and can be attacked over the network without a login.
Affected products
Basic Pdu Firmware, Pm Pdu Firmware, Piml Pdu Firmware, Smart Pim Firmware, Smart Pos Firmware, Smart Pom Firmware, Smart Poms Firmware. The exact versions are in the references.
What to do now
- Check your exposureFind out whether Powertekpdus Basic Pdu Firmware runs anywhere in your environment, including systems of suppliers.
- UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
- Limit access until thenIf you cannot update at once, take the system off the internet or restrict who can reach it.
References
Data: CVE list and the NVD. This product uses data from the NVD API but is not endorsed or certified by the NVD.