Vulnerabilities · 2023 · Omron
CVE-2023-27396
Omron Cs1w-eip21 Firmware vulnerability
FINS (Factory Interface Network Service) is a message communication protocol, which is designed to be used in closed FA (Factory Automation) networks, and is used in FA networks composed of OMRON products. Multiple OMRON products that implement FINS protocol contain following security issues -- (1)Plaintext communication, and (2)No authentication required. When FINS messages are intercepted, the contents may be retrieved. When arbitrary FINS messages are injected, any commands may be executed on, or the system information may be retrieved from, the affected device. Affected products and versions are as follows: SYSMAC CS-series CPU Units, all versions, SYSMAC CJ-series CPU Units, all versions, SYSMAC CP-series CPU Units, all versions, SYSMAC NJ-series CPU Units, all versions, SYSMAC NX1P-series CPU Units, all versions, SYSMAC NX102-series CPU Units, all versions, and SYSMAC NX7 Database Connection CPU Units (Ver.1.16 or later)
High priority: this vulnerability is rated critical and can be attacked over the network without a login.
Affected products
Cs1w-eip21 Firmware, Cs1w-spu01-v2 Firmware, Cs1w-spu02-v2 Firmware, Cs1w-etn21 Firmware, Cs1w-clk Firmware, Cs1w-fln22 Firmware, Cs1w-drm21-v1 Firmware, Cs1w-nc271 Firmware, Cs1w-nc471 Firmware, Cs1w-ncf71 Firmware and more. The exact versions are in the references.
What to do now
- Check your exposureFind out whether Omron Cs1w-eip21 Firmware runs anywhere in your environment, including systems of suppliers.
- UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
- Limit access until thenIf you cannot update at once, take the system off the internet or restrict who can reach it.
References
- www.fa.omron.co.jp/product/vulnerability/OMSR-2023-003_ja.pdf · Vendor Advisory
- www.ia.omron.com/product/vulnerability/OMSR-2023-003_en.pdf · Vendor Advisory
- jvn.jp/en/ta/JVNTA91513661/ · Third Party Advisory
- jvn.jp/ta/JVNTA91513661/ · Third Party Advisory
- www.cisa.gov/uscert/ics/advisories/icsa-22-179-02 · Third Party Advisory
- www.us-cert.gov/ics/advisories/icsa-19-346-02 · Third Party Advisory
- www.us-cert.gov/ics/advisories/icsa-20-063-03 · Third Party Advisory
- nvd.nist.gov/vuln/detail/CVE-2023-27396
- cve.org/CVERecord?id=CVE-2023-27396
More vulnerabilities in Omron products
Data: CVE list and the NVD. This product uses data from the NVD API but is not endorsed or certified by the NVD.