CVE-2024-1573
Missing Authentication for Critical Function vulnerability in the …
Missing Authentication for Critical Function vulnerability in the mobile monitoring feature of Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.2, Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.2, Mitsubishi Electric Iconics Digital Solutions ICONICS Suite versions 10.97 to 10.97.2, Mitsubishi Electric ICONICS Suite versions 10.97 to 10.97.2, and Mitsubishi Electric MC Works64 all versions allows a remote unauthenticated attacker to bypass proper authentication and log in to the system when all of the following conditions are met: * Active Directory is used in the security setting. * “Automatic log in” option is enabled in the security setting. * The IcoAnyGlass IIS Application Pool is running under an Active Directory Domain Account. * The IcoAnyGlass IIS Application Pool account is included in GENESIS64 and MC Works64 Security and has permission to log in.
What to do now
- Check your exposureFind out whether the affected software runs anywhere in your environment, including systems of suppliers.
- UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
- Limit access until thenIf you cannot update at once, take the system off the internet or restrict who can reach it.
References
Data: CVE list and the NVD. This product uses data from the NVD API but is not endorsed or certified by the NVD.