CVE-2026-124760
P-Net before 1.0.4 sets the alarm receiver state to waiting for …
P-Net before 1.0.4 sets the alarm receiver state to waiting for confirmation before the data of a received alarm notification is parsed. If the parsing fails the state is not restored, and later alarm notifications of the same priority are discarded without acknowledge until the Application Relationship is released. The Application Relationship and the cyclic data exchange keep working. The attacker must be able to send an alarm notification in the context of an established Application Relationship and requires ADJACENT network access.
What to do now
- Check your exposureFind out whether the affected software runs anywhere in your environment, including systems of suppliers.
- UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
- Set the orderSystems that can be reached from the internet come first, then the rest.
References
Data: CVE list and the NVD. This product uses data from the NVD API but is not endorsed or certified by the NVD.