Vulnerabilities · 2018 · Eaton
CVE-2018-16158
Eaton Power Xpert Meter 4000 Firmware vulnerability
Eaton Power Xpert Meter 4000, 6000, and 8000 devices before 13.4.0.10 have a single SSH private key across different customers' installations and do not properly restrict access to this key, which makes it easier for remote attackers to perform SSH logins (to uid 0) via the PubkeyAuthentication option.
High priority: this vulnerability is rated critical and can be attacked over the network without a login.
Affected products
Power Xpert Meter 4000 Firmware, Power Xpert Meter 6000 Firmware, Power Xpert Meter 8000 Firmware. The exact versions are in the references.
What to do now
- Check your exposureFind out whether Eaton Power Xpert Meter 4000 Firmware runs anywhere in your environment, including systems of suppliers.
- UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
- Limit access until thenIf you cannot update at once, take the system off the internet or restrict who can reach it.
References
- www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/PXM · Vendor Advisory
- www.ctrlu.net/vuln/0006.html · Exploit
- github.com/BrianWGray/msf/blob/master/exploits/linux/ssh/eaton_known_privkey.rb · Exploit
- nvd.nist.gov/vuln/detail/CVE-2018-16158
- cve.org/CVERecord?id=CVE-2018-16158
More vulnerabilities in Eaton products
CVE-2024-31416CVE-2024-31415CVE-2024-31414CVE-2023-43777CVE-2023-43776CVE-2023-43775CVE-2022-33859CVE-2021-23288All 44
Data: CVE list and the NVD. This product uses data from the NVD API but is not endorsed or certified by the NVD.