Vulnerabilities · 2019 · Abb
CVE-2019-7225
Abb Cp620 Firmware vulnerability
The ABB HMI components implement hidden administrative accounts that are used during the provisioning phase of the HMI interface. These credentials allow the provisioning tool "Panel Builder 600" to flash a new interface and Tags (MODBUS coils) mapping to the HMI. These credentials are the idal123 password for the IdalMaster account, and the exor password for the exor account. These credentials are used over both HTTP(S) and FTP. There is no option to disable or change these undocumented credentials. An attacker can use these credentials to login to ABB HMI to read/write HMI configuration files and also to reset the device. This affects ABB CP635 HMI, CP600 HMIClient, Panel Builder 600, IDAL FTP server, IDAL HTTP server, and multiple other HMI components.
Affected products
Cp620 Firmware, Cp620-web Firmware, Cp630 Firmware, Cp630-web Firmware, Cp635 Firmware, Cp635-b Firmware, Cp635-web Firmware, Pb610 Firmware, Cp651-web Firmware, Cp661 Firmware and more. The exact versions are in the references.
What to do now
- Check your exposureFind out whether Abb Cp620 Firmware runs anywhere in your environment, including systems of suppliers.
- UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
- Set the orderSystems that can be reached from the internet come first, then the rest.
References
- www.darkmatter.ae/xen1thlabs/abb-hmi-hardcoded-credentials-vulnerability-xl-19-009/ · Exploit
- packetstormsecurity.com/files/153397/ABB-HMI-Hardcoded-Credentials.html · Third Party Advisory
- seclists.org/fulldisclosure/2019/Jun/38 · Third Party Advisory
- www.securityfocus.com/bid/108922 · Third Party Advisory
- nvd.nist.gov/vuln/detail/CVE-2019-7225
- cve.org/CVERecord?id=CVE-2019-7225
More vulnerabilities in Abb products
Data: CVE list and the NVD. This product uses data from the NVD API but is not endorsed or certified by the NVD.