CONTENTUM.COMA specialist. A plan. A result.

Vulnerabilities · 2015 · Siemens

CVE-2015-5374
Siemens Siprotec Firmware vulnerability

A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Specially crafted packets sent to port 50000/UDP could cause a denial-of-service of the affected device. A manual reboot may be required to recover the service of the device.

Affected products

Siprotec Firmware. The exact versions are in the references.

What to do now

  • Check your exposureFind out whether Siemens Siprotec Firmware runs anywhere in your environment, including systems of suppliers.
  • UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
  • Limit access until thenIf you cannot update at once, take the system off the internet or restrict who can reach it.

References

More vulnerabilities in Siemens products

Data: CVE list and the NVD. This product uses data from the NVD API but is not endorsed or certified by the NVD.