CONTENTUM.COMA specialist. A plan. A result.

Vulnerabilities · 2022 · Honeywell

CVE-2022-30313
Honeywell Safety Manager Firmware vulnerability

Honeywell Experion PKS Safety Manager through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0051, there is a Honeywell Experion PKS Safety Manager multiple proprietary protocols with unauthenticated functionality issue. The affected components are characterized as: Honeywell Experion TCP (51000/TCP), Safety Builder (51010/TCP). The potential impact is: Manipulate controller state, Manipulate controller configuration, Manipulate controller logic, Manipulate controller files, Manipulate IO. The Honeywell Experion PKS Distributed Control System (DCS) Safety Manager utilizes several proprietary protocols for a wide variety of functionality, including process data acquisition, controller steering and configuration management. These protocols include: Experion TCP (51000/TCP) and Safety Builder (51010/TCP). None of these protocols have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality. There is no authentication functionality on the protocols in question. An attacker capable of invoking the protocols' functionalities could achieve a wide range of adverse impacts, including (but not limited to), the following: for Experion TCP (51000/TCP): Issue IO manipulation commands, Issue file read/write commands; and for Safety Builder (51010/TCP): Issue controller start/stop commands, Issue logic download/upload commands, Issue file read commands, Issue system time change commands. A mitigating factor with regards to some, but not all, of the above functionality is that these require the Safety Manager physical keyswitch to be in the right position.

Affected products

Safety Manager Firmware. The exact versions are in the references.

What to do now

  • Check your exposureFind out whether Honeywell Safety Manager Firmware runs anywhere in your environment, including systems of suppliers.
  • UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
  • Limit access until thenIf you cannot update at once, take the system off the internet or restrict who can reach it.

References

More vulnerabilities in Honeywell products

Data: CVE list and the NVD. This product uses data from the NVD API but is not endorsed or certified by the NVD.