Siemens Desigo Web Module Pxa30-w0 Firmware vulnerability

Siemens Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 for Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D (All firmware versions < V6.00.046) and Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 for Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U (All firmware versions < V6.00.046) use a pseudo random number generator with insufficient entropy to generate certificates for HTTPS, potentially allowing remote attackers to reconstruct the corresponding private key.

Affected products

Desigo Web Module Pxa30-w0 Firmware, Desigo Web Module Pxa30-w1 Firmware, Desigo Web Module Pxa30-w2 Firmware, Desigo Web Module Pxa40-w0 Firmware, Desigo Web Module Pxa40-w1 Firmware, Desigo Web Module Pxa40-w2 Firmware. The exact versions are in the references.

What to do now

  • Check your exposureFind out whether Siemens Desigo Web Module Pxa30-w0 Firmware runs anywhere in your environment, including systems of suppliers.
  • UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
  • Limit access until thenIf you cannot update at once, take the system off the internet or restrict who can reach it.

References

More vulnerabilities in Siemens products