Vulnerabilities · 2016 · Siemens
CVE-2016-9154
Siemens Desigo Web Module Pxa30-w0 Firmware vulnerability
Siemens Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 for Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D (All firmware versions < V6.00.046) and Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 for Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U (All firmware versions < V6.00.046) use a pseudo random number generator with insufficient entropy to generate certificates for HTTPS, potentially allowing remote attackers to reconstruct the corresponding private key.
Affected products
Desigo Web Module Pxa30-w0 Firmware, Desigo Web Module Pxa30-w1 Firmware, Desigo Web Module Pxa30-w2 Firmware, Desigo Web Module Pxa40-w0 Firmware, Desigo Web Module Pxa40-w1 Firmware, Desigo Web Module Pxa40-w2 Firmware. The exact versions are in the references.
What to do now
- Check your exposureFind out whether Siemens Desigo Web Module Pxa30-w0 Firmware runs anywhere in your environment, including systems of suppliers.
- UpdateInstall the version in which the vendor fixed the vulnerability. The references lead to the advisory.
- Limit access until thenIf you cannot update at once, take the system off the internet or restrict who can reach it.
References
- www.siemens.com/cert/pool/cert/siemens_security_advisory_ssa-856492.pdf · Mitigation
- www.securityfocus.com/bid/94962 · Third Party Advisory
- ics-cert.us-cert.gov/advisories/ICSA-16-355-01 · Third Party Advisory
- nvd.nist.gov/vuln/detail/CVE-2016-9154
- cve.org/CVERecord?id=CVE-2016-9154
More vulnerabilities in Siemens products
Data: CVE list and the NVD. This product uses data from the NVD API but is not endorsed or certified by the NVD.